'35.YA' Start of manipulated variable limit / '36.YE' End of manipulated variable limit

Adjustment range:
Purpose:
Factory setting:
Note
'YE' must always be set larger than 'YA'.
9.4.2.9

'37.YNRM' Standardization of manipulated variable

Possible settings:
Purpose:
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC
0.0 ... 100.0
These parameters are used to limit the mechanical actuator travel
from stop to stop to the configured values. The value is given in
percent. This allows the mechanical travel range of the actuator to
be limited to the effective flow, preventing integral saturation of the
controlling closed-loop controller.
See the figure in the description of the '37.YNRM' Standardization
of manipulated variable (Page 155) parameter.
'Dead angle' function
The dead angle is the angle range in which the process valve allows
no flow. The dead angle range starts at the lower endstop of the
valve, for example, and ends at the angle at which the medium be‐
gins to flow. Use this function if you want to use the entire signal
range for valve control (for example, 4 to 20 mA).
To now use the entire signal range for valve control (for example,
of ball and segment valves), set the low limit of the manipulated
variable (YA) to the percentage at which the medium begins to flow.
To display the new start value as 0%, set '37.YNRM' Standardization
of manipulated variable (Page 155) to 'FloW'.
When 'YA': 0.0
● MPOS
● FLoW
Use the '35.YA' Start of manipulated variable limit / '36.YE' End of
manipulated variable limit (Page 155) parameters to limit the ma‐
nipulated variable. This limitation causes two different scaling types
'MPOS' and 'FLoW' for the display and for the position feedback
through the current output.
The MPOS scale shows the mechanical positions from 0 to 100%
between the upper and lower endstops of the initialization. The po‐
sition is not influenced by the '35.YA' Start of manipulated variable
limit / '36.YE' End of manipulated variable limit (Page 155) parame‐
ters. The 'YA' and 'YE' parameters are shown in the MPOS scale.
Parameter assignment
9.4 Description of parameters
When 'YE': 100.0
155