A7 Swing Flap Motor (M1S) Abnormality - Daikin VRVII Manual

Vrv series pocket manual
Hide thumbs Also See for VRVII:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
A7
3.7
Abnormality
Remote Controller Display
A7
Applicable Models
R-22: FXC, FXA, FXF, FXH, FXK
R-410A: FXCQ, FXHQ, FXKQ, FXUQ
Method of Error Detection
Utilizes ON/OFF of the limit switch when the motor turns.
Error Decision Conditions
When ON/OFF of the micro-switch for positioning cannot
be reversed even though the swing flap motor is
energized for a specified amount of time (about 30
seconds).
∗ Error code is displayed but the system operates
continuously.
Supposed Causes
Defective swing motor
Defective connection cable (power supply and limit
switch)
Defective airflow direction adjusting flap-cam
Defective indoor unit PCB
Swing Flap Motor (M1S)
63