F6 Refrigerant Overcharged - Daikin VRVII Manual

Vrv series pocket manual
Hide thumbs Also See for VRVII:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
F6
3.31
Remote Controller Display
F6
Applicable Models
VRVIII, III-S and III-Q Series
Method of Error Detection
Excessive charging of refrigerant is detected by using the
outdoor air temperature, heat exchanger deicer
temperature and liquid pipe temperature during check
operation.
Error Decision Conditions
When the amount of refrigerant, which is calculated by
using the outdoor air temperature, heat exchanging
deicer temperature and liquid pipe temperature during
check operation, exceeds the criteria.
Supposed Causes
Refrigerant overcharge
Disconnection of outdoor air thermistor
Disconnection of heat exchanger deicer thermistor
Defective liquid pipe thermistor
Refrigerant Overcharged
143