4.1.4 P/F SHOTS sub-menu

This menu allows the Phase fault trip/reclose sequence to be parameterized:-
79 P/F Prot'n Trip1
79 P/F Deadtime 1
79 P/F Prot'n Trip2
79 P/F Deadtime 2
79 P/F Prot'n Trip3
79 P/F Deadtime 3
79 P/F Prot'n Trip 4
79 P/F Deadtime 4
79 P/F Prot'n Trip5
79 P/F HighSet Trips to Lockout Sets the number of allowed HighSet trips. The relay will go to
79 P/F Delayed Trips to Lockout Sets the number of allowed Delayed trips, Relay will go to Lockout

4.1.5 E/F SHOTS sub-menu

This menu allows the Earth Fault trip/reclose sequence to be parameterized:-
As above but E/F settings.

4.1.6 SEF SHOTS sub-menu

This menu allows the Sensitive Earth trip/reclose sequence to be parameterized:-
As above but SEF Settings, Note: - SEF does not have HighSets
©2009 Siemens Protection Devices Limited
The first protection Trip in the P/F sequence can be set to either Inst or
Delayed.
Sets the first Reclose Delay (Dead time) in the P/F sequence.
The second protection Trip in the P/F sequence can be set to either Inst or
Delayed.
Sets the second Reclose Delay (Dead time) in the P/F sequence.
The third protection Trip in the P/F sequence can be set to either Inst or
Delayed.
Sets the third Reclose Delay (Dead time) in the P/F sequence.
The fourth protection Trip in the P/F sequence can be set to either Inst or
Delayed.
Sets the fourth Reclose Delay (Dead time) in the P/F sequence.
The fifth and last protection Trip in the P/F sequence can be set to either Inst
or Delayed.
Lockout on the last HighSet Trip. This function can be used to limit the
duration and number of high current trips that the Circuit Breaker is required
to perform, if the fault is permanent and close to the Circuit Breaker then there
is no point in forcing a number of Delayed Trips before the Relay goes to
Lockout – that sequence will be truncated.
on the last Delayed Trip. This function limits the number of Delayed trips that
the Relay can perform when the Instantaneous protection Elements are
externally inhibited for system operating reasons - sequences are truncated.