(1) Description of Operation 7SR224
3.8
C
P
: U
-C
(37)
URRENT
ROTECTION
NDER
URRENT
Two under-current elements are provided.
Each phase has an independent level detector and current-timing element. 37-n Setting sets the pick-
up current. An output is given after elapse of the 37-n Delay setting.
Operation of the under-current elements can be inhibited from:
A binary or virtual input.
Inhibit 37-n
Figure 3.8-1
Logic Diagram: Undercurrent Detector (37)
©2009 Siemens Protection Devices Limited