Current Protection: High Impedance Restricted Earth Fault (64H); Figure 3.5-1 Logic Diagram: High Impedance Ref (64H) - Siemens 7SR224 Description & Operation

Recloser controller
Hide thumbs Also See for 7SR224:
Table of Contents

Advertisement

(1) Description of Operation 7SR224
3.5
C
P
URRENT
One high impedance Restricted Earth Fault (REF) element is provided.
The relay utilises fundamental current measurement values for this function.
The single phase current input is derived from the residual output of line/neutral CTs connected in
parallel. An external stabilising resistor must be connected in series with this input to ensure that this
element provides a high impedance path. If I
used.
64H Current Setting sets the pick-up current level. An output is given after elapse of the 64H Delay
setting.
External components – a series stabilising resistor and a non-linear resistor – are used with this
function. See 'Applications Guide' for advice in specifying suitable component values.
Operation of the high impedance element can be inhibited from:
Inhibit 64H
64H Element
Enabled
Disabled
Inhibit 64H