EIB / KNX
Commissioning
Data type of threshold value object
Options:
1 bit/1 byte [0...255]
If the 1 bit option is set for the Data type of threshold value object parameter,
the following parameters appear.
Send if signal OFF
Options:
Do not send a telegram
Send an ON telegram
Send an OFF telegram
Send if signal ON
Options:
Do not send a telegram
Send an ON telegram
Send an OFF telegram
Option Do not send a telegram = No reaction occurs
Option Send an ON telegram = Send telegram value "1"
Option Send an OFF telegram = Send telegram value "0"
Minimum duration for signal OFF
Minimum duration for signal ON
Options:
none/5 s/10 s/30 s/1 min/5 min/10 min/30 min/1 h/6 h/
12 h/24 h
Option none = Send threshold value directly
The further time options can be used to select a minimum duration. If the
send condition reverts within the minimum duration, no telegram is sent.
If the 1 byte [0...255] option is set for the Data type of threshold value object
parameter, the following parameters appear.
Send if signal OFF [0...255]
Options:
0...255
Send if signal ON [0...255]
Options:
0...255
A value of 0 to 255 can be entered in single steps.
Minimum duration for signal OFF
Minimum duration for signal ON
Options:
none/5 s/10 s/30 s/1 min/5 min/10 min/30 min/1 h/6 h/
12 h/24 h
Option none = Send threshold value directly
The further time options can be used to select a minimum duration. If the
send condition reverts within the minimum duration, no telegram is sent.