Figure 5-17 Diagram Of Power Wire & Control Wire Connections For 3-4 Units In Mms Config - Toshiba G9000 SERIES Installation And Operation Manual

480/480 v 100/160/225/300/500/750 kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

Figure 5-17 Diagram of Power Wire & Control Wire Connections for 3-4 units in MMS Config. (300-750kVA)
NOTE
Use Ethernet STP
(Shielded Twisted Pair)
Cable (Cat 5 or better)
with shielded RJ45
modular connectors for
all communication
cabling.
Use of UTP (Unshielded
Twisted Pair) Cable may
cause malfunction.
Total cable length
from UPS-1 to UPS-n
should be within
100m.
*1 Return from the last
UPS module to the first UPS
module (continuous loop).
*2 DIP switch position
UPS-1 and UPS-n: ON
Otherwise: OFF
*3 n = 3-4 (maximum) for this
cabling configuration
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
UPS-1
Communication
IFAU-09
Cabling
CN99
TLBIN
*1
CN98
TLAIN
*1
CN97
TLBOUT
CN96
TLAOUT
*2
ON
CN954
CB2IN
CN953
CB1IN
CN952
CA2IN
CN951
CA1IN
CN944
CB2OUT
CN943
CB1OUT
CN942
CA2OUT
CN941
CA1OUT
ON
*2
UPS-2
IFAU-09
CN99
TLBIN
CN98
TLAIN
CN97
TLBOUT
CN96
TLAOUT
*2
OFF
CN954
CB2IN
CN953
CB1IN
CN952
CA2IN
CN951
CA1IN
CN944
CB2OUT
CN943
CB1OUT
CN942
CA2OUT
CN941
CA1OUT
*2
OFF
UPS-n
*3
IFAU-09
CN99
TLBIN
CN98
TLAIN
CN97
TLBOUT
CN96
TLAOUT
*2
ON
CN954
CB2IN
CN953
CB1IN
CN952
CA2IN
CN951
CA1IN
CN944
CB2OUT
CN943
CB1OUT
CN942
CA2OUT
CN941
CA1OUT
*2
ON
IOAU-09
TN1
5
6
AC
OUTPUT
A50
B50
C50
IOAU-09
TN1
5
6
AC
OUTPUT
A50
B50
C50
IOAU-09
TN1
5
6
AC
OUTPUT
A50
B50
C50
Toshiba Tie Cabinet (TTC)
Control
Cabling
35
52L1-AX
36
37
52L2-AX
38
.
.
.
49
52Ln-AX
50
*3
Power
Cabling
AC OUTPUT
UPS-1
A
B
C
UPS-2
A
B
C
.
.
.
UPS-n
*3
A
B
C