Internal Switch Settings
E5CJ
Top view
2-3-2 Input Type Selector Setting
Selector no.
0, 8
JPt100
1, 9
Pt100
2
K
3
J
4
T
5
L
6
U
7
N
1, 2, 3...
12
ALM2
Alarm mode selector 2
ALM1
Alarm mode selector 1
INPUT
Input type selector
Note The E5CJ with no alarm does not incorporate ALM1 or ALM2.
The input type selector is factory-set to 2 (K). Refer to the following table for the selection
of the desired sensor.
Input
Set temperature range
C
–199.9 to 650.0
–199.9 to 650.0
–200 to 1300
–100 to 850
–199.9 to 400.0
–100 to 850
–199.9 to 400.0
–200 to 1300
Note The resistance of the JPt100 at a temperature of 100 C is 139.16 Ω and that of
the Pt100 at a temperature of 100 C is 138.50 Ω.
1. To use Fahrenheit, set function selector 4 to ON, which is usually set to OFF.
2. Insert the internal mechanism into the case.
3. Turn on the E5jJ so that d-u will be displayed on the process value display.
Then press the Up Key so that f will be displayed on the set value display.
4. Turn off the power in two seconds.
5. Draw the internal mechanism from the case and set function selector 4 to
OFF and turn on the E5jJ.
Bottom view
PROTECT
Key protection
switch
FUNCTION
Function selector
INPUT
Specified temperature range
F
–199.9 to 999.9
–199.9 to 735.0
–199.9 to 999.9
–199.9 to 735.0
–300 to 2300
–350 to 1450
–100 to 1500
–195 to 945
–199.9 to 700.0
–199.9 to 460.0
–100 to 1500
–195 to 945
–199.9 to 700.0
–199.9 to 460.0
–300 to 2300
–350 to 1450
Section 2-3
SP
OFF
ALL
C
F
–199.9 to 999.9
–199.9 to 999.9
–560 to 2560
–260 to 1660
–199.9 to 790.0
–260 to 1660
–199.9 to 790.0
–560 to 2560