Chapter 1 Safety Instructions

1.3 Precautions Concerning Compliance with UL and cUL Standards

(Standard to comply with : UL508C,CSA C22.2 No.14-05)
a) Maximum surrounding air temperature rating of 50ºC.
b) Solid State motor overload protection reacts with max. 150 % of FLA.
c) Suitable for use on a circuit capable of delivering not more than 100,000 rms Symmetrical Amperes,
240 Volts Maximum. For models 200V class.
Suitable for use on a circuit capable of delivering not more than 100,000 rms Symmetrical Amperes,
480 Volts Maximum.For models 400V class.
d) Drive has no provision for motor over temperature protection.
e) When protected by J, CC, G or T Class Fuses. or When protected by a circuit breaker having an
interrupting rating not less than 100,000 rms symmetrical amperes, 240 Volts maximum. For models
200V class.
When Protected by J, CC, G or T Class Fuses. For models 400V class.
f)
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit
protection must be provided in accordance with the National Electrical Code and any additional local
codes.
g) Install device in pollution degree 2 environment
h) Branch circuit short circuit protection can use fuse or circuit breaker only. For models 200V class..
Branch circuit short circuit protection can use fuse only. For models 400V class..
i)
Use 60/75ºC CU wire only.
j)
Tightening torque and wire range as shown in the table below.
NES1-002S,004S
NES1-002L,004L,007L
NES1-004H,007H,015H
NES1-022H,040H
j)
Distribution fuse and circuit breaker size marking is included in the manual to indicate that the unit
shall be connected with a Listed Cartridge Nonrenewable fuse or Inverse time circuit breaker, rated
600 VAC with the current ratings as shown in the table below:
Model No.
NES1-002S,004S
NES1-007S
NES1-015S,022S
NES1-002L*,004L*
NES1-004L*
NES1-007L*,015L
NES1-022L
NES1-004H,007H,
015H,022H,040H
* In case of using Circuit Breaker, an additional 5 A external protector is needed.
Wiring diagram of inverter
Circuit breaker or
Fuse
Power
supply
Model No.
Required Torque (N.m)
NES1-007S
NES1-015S
NES1-022S
NES1-015L
NES1-022L
Fuse
Type
Class J, CC, G or T
Class J, CC, G or T
Class J, CC, G or T
DC link choke
P
PD
R
U
Motor
S
V
W
T
Inverter
0.8~1.0
1.8
1.8
1.8
0.8~1.0
1.8
1.8
1.8
1.8
Maximum Rating
10 A
20 A
30 A
10 A
15 A
20 A
15A
1 - 10
Wire Range(AWG)
16~14
14~12
12~10
10
16~14
14
12
16
14
Circuit Breaker
Type
Maximum Rating
15 A
Inverse
Time
30 A
Inverse
15 A
Time
20 A
-
-