CONFIGURATION Menu

The electronically controlled unit has many operating functions whose settings are preset at the factory. The following
configuration programming steps are provided for those cases where the modules have been replaced after the unit has
been in operation and must be reconfigured.
Refer to the Model number stamped on the unit nameplate located on the control panel door while scrolling through the
configuration screens. Certain digits of this alpha/numeric model number provide information that must be entered at the
Human Interface (HI) in order for the UCM network to operate properly.
Notes:
1. Prior to making any changes to these Configuration Menus, the Stop key must be pressed on the Local Human
Interface.
2. Many of the screens displayed in this section are applicable only for the options that are installed in the unit and may
not be visible on your unit. All screens displayed with "CONFIG REQ'D" are required to be changed prior to unit
operation.
3. Pay close attention to the notes throughout this section of the document. The notes describe additional essential
messages and other intermediate screen information.
Modifying Selections:
appropriate keys to navigate (Next and Previous) and make changes (+ and -) to the selections. Once the selection has
been changed to the desired value, the user has the following options to either Cancel or Accept the pending change:
To Cancel, press the Cancel key to remove the change, the display will revert to the original value.
To Accept, press the Enter key to confirm the new choice.
Press the Configuration key to begin viewing or modifying the configuration screens.
TOP LEVEL CONFIGURATION SCREEN
Unit Product Family is:
Press (NEXT) or (PREVIOUS) to Continue
Note: "Product Family" is based on the absence (INTELLIPAK), or
presence (INTELLIPAK II), of a configuration jumper in the wire
harness of the RTM module.
• Press Next/Previous keys to navigate.
Configuration - Model Num Digit
Unit Type:
Note:
1. For INTELLIPAK II products, if "Unit Type" is changed "Unit
Capacity" below is set to CONFIG REQ'D.
2. If "Heating Type" below is Electric Heat, the "Electric Heat
Capacity" below is also set to CONFIG. REQ'D.
• Press Next/Previous keys to navigate.
RT-SVP07B-EN
Starting with the first configuration screen program the necessary information by using the
INTELLIPAK II
ROOFTOP UNIT
Used With: All Units
Possible Values:
INTELLIPAK
INTELLIPAK II
Note: This screen is not adjustable.
Used With: All Units
1
Possible Values:
ROOFTOP UNIT
AIR HANDLER
97