Software Compatibility; Commissioning; Setting The Loop To Manual - Emerson Rosemount 3144P Reference Manual

Temperature transmitter with rosemount x-well technology
Hide thumbs Also See for Rosemount 3144P:
Table of Contents

Advertisement

Installation
April 2017
2.2.6

Software compatibility

Replacement transmitters may contain revised software that is not fully compatible with the existing
software. The latest device descriptors (DD) are available with new Field Communicators or they can be
loaded into existing communicators at any Emerson Service Center or via the Easy Upgrade process. For
more information on upgrading a Field Communicator, see
To download new device drivers, visit
2.3

Commissioning

The Rosemount 3144P Transmitter must be configured for certain basic variables to operate. In many
cases, these variables are pre-configured at the factory. Configuration may be required if the variables
need to be changed.
Commissioning consists of testing the transmitter and verifying transmitter configuration data.
transmitters can be commissioned either before or after installation. Commissioning the transmitter on
the bench before installation using a Field Communicator or AMS Device Manager ensures that all
transmitter components are in working order.
For more information on using the Field Communicator with the transmitter, see
Commissioning. For more information on using the Rosemount 3144 with F
Section 4: Foundation Fieldbus
Figure 2-2. Installation Flowchart
START HERE
2.3.1

Setting the loop to manual

Set the process application loop to manual when sending or requesting data that would disrupt the loop
or change the output of the transmitter. The Field Communicator or AMS Device Manager will prompt to
set the loop to manual, when necessary. Acknowledging the prompt does not set the loop to manual, it
is only a reminder. Setting the loop to manual is a separate operation.
10
Emerson.com/Rosemount/Device-Install-Kits.
Configuration.
Bench
No
Calibration?
Yes
BASIC SETUP
Set Units
Simulate Sensor
Set Sensor Types
Set Number of
Wires
Set Range
Values - HART
5: Operation and
Set Damping
Section 3: HART
VERIFY
Input
Yes
Within
Specifications?
No
Check for Process
Refer to
Section
Maintenance
Reference Manual
00809-0100-4021, Rev JA
Commissioning.
Section 3: HART
Fieldbus, see
OUNDATION
FIELD INSTALL
Set Jumpers or
Switches
Mount the
Transmitter
Wire the
Transmitter
Power the
Transmitter
Leaks
Done
Installation