Additional clearances

Check on whether local codes supersede these clearances.
Avoid termination locations near a dryer vent.
Avoid termination locations near commercial
cooking exhaust.
You must install a vent termination at least 12
inches above grade or snow line.
The vent for this appliance shall not terminate
Over public walkways; or
Near soffit vents or crawl space vents or other
area where condensate or vapor could create a
nuisance or hazard or cause property damage; or
Where condensate or vapor could cause damage
or could be detrimental to the operation of
regulators, relief valves, or other equipment.
Important considerations for locating vent
termination under a soffit (ventilated or unventilated
or eave vent; or to a deck or porch)
Do not install vent termination under a soffit vent
such that exhaust can enter the soffit vent
Install vent termination such that exhaust and
rising moisture will not collect under
eaves. Discoloration to the exterior of the
building could occur if installed too close.
Do not install the vent termination too close
under the soffit where it could present
recirculation of exhaust gases back into the
combustion air intake part of the termination.
Represents the exhaust vent of CVent
V
common venting.
(0.91 m)
between
terminals at
different levels
60"
36"
V
V
24"
36"
15
(0.61 m ) to an inside corner
24"
V
V
36"
(0.91 m) between
terminals at same
level
INSIDE
CORNER
(0.61 m) to wall or parapet
V
(0.91 m) between
terminals at same
level
Rinnai CVent