Fujitsu WATERSTAGE 112 Maintenance Document page 84

Waterstage series 3 phase air/water heat pump split system, single service
Hide thumbs Also See for WATERSTAGE 112:
Table of Contents

Advertisement

Heat Pump, Split System, Single Service, 3 phase
Summer Compensation
Line no.
Programming line
918
Summer comp start at OT
919
Summer comp end at OT
920
Summer comp setp increase
In summer the "cooling comfort setpoint" (902) is
gradually
increased
temperature. This saves on cooling power and
prevents the differences between the ambient
temperature of the room and the outdoor temperature
being too high.
The resulting "room temperature setpoint" (cooling)
can be viewed in the Info section.
Summer compensation start at OT
Summer compensation starts to be active from the
outdoor temperature defined here. If the outdoor
temperature continues to rise, the comfort setpoint
will be gradually increased.
84
according
to
the
outdoor
Comfort
setpoint
902
918
Summer compensation end at OT
At
this
outdoor
compensation reaches its peak efficiency (920). If the
outdoor temperature continues to rise, it will no longer
influence the comfort setpoint.
Summer compensation setpoint increase
This setting defines the highest value to which the
comfort setpoint can be increased.
920
OT
919
temperature
the
summer
Maintenance Document 1394-1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Waterstage 140Waterstage 160

Table of Contents