Fujitsu WATERSTAGE 112 Maintenance Document page 32

Waterstage series 3 phase air/water heat pump split system, single service
Hide thumbs Also See for WATERSTAGE 112:
Table of Contents

Advertisement

Heat Pump, Split System, Single Service, 3 phase
Clear 9: Outdoor temperature thermistor error
Hydraulic Unit LED: Green 7 flashes / Red 4 flashes
Outdoor Unit LED: 7 flashes
Probable causes:
Misconnection.
Sensor failure.
Main PCB failure.
Check:
1. Check the sensor connection :
See if the connector has been disconnected.
-
See if the connection is correct.
-
Check for any damage on the sensor cable.
-
After solving the misconnection problem, switch the heat pump back on.
2. Remove the sensor and check its resistance value :
- Check the resistance value.
Temperature (°C)
Resistance (kΩ)
115 62,3 46,6 35,2 26,9 20,7 16,1 12,6 7,97 5,18 3,45 2,36 1,65
- If the thermistor is faulty, replace it.
3. Check the electronic board voltage:
- Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
- If there is no voltage, replace Main PCB.
32
OK
-20
-10
-5
0
OK
5
10
15
20
30
40
50
60
Maintenance Document 1394-1