4.1.2 Outdoor Unit Fault

When the system is switched back on after a power
outage, the Hydraulic Unit may display fault 370 for a
few tens of seconds. This is not a serious problem. It
simply means that the outdoor unit is running its
tests. Once the tests have been completed, the fault
should disappear.
On the outdoor unit
When an error occurs:
-
The diode "ERROR" (2) blinks
Press once on the switch "ENTER" (SW4)
-
The "ERROR" (2) diode blinks several times depending on the error's type
Location of switches and diodes on outdoor unit
LED display
Hydraulic Unit
Green
Red
1 flash
1 flash
4 flashes
1 flash
4 flashes
2 flashes
6 flashes
3 flashes
6 flashes
4 flashes
7 flashes
1 flash
7 flashes
2 flashes
7 flashes
3 flashes
7 flashes
4 flashes
7 flashes
7 flashes
7 flashes
8 flashes
8 flashes
6 flashes
9 flashes
4 flashes
9 flashes
5 flashes
9 flashes
7 flashes
10 flashes 1 flash
10 flashes 3 flashes
10 flashes 5 flashes
Maintenance Document 1394-1
Diagnosis
Outdoor unit
Off
Serial reverse transfer error.
1 flash
Serial forward transfer error.
22 flashes
Heat pump capacity signal error
22 flashes
Hydraulic Unit Heat ex. Sensor error
18 flashes
Inverter error.
19 flashes
P.F.C. error.
2 flashes
Discharge thermistor error.
8 flashes
Compressor thermistor error.
5 flashes
Heat-exchange thermistor (intermediate) error.
4 flashes
Heat-exchange thermistor (outlet) error.
7 flashes
Outdoor temperature thermistor error.
9 flashes
Heat sink thermistor (inverter) error.
10 flashes
Heat sink thermistor (P.F.C.) error.
6 flashes
Expansion valve thermistor error.
3 flashes
Pressure sensor error.
13 flashes
Current trip (permanent stoppage).
14 flashes
Detection of compressor position error (permanent stoppage).
15 flashes
Compressor start up error (permanent stoppage).
16 flashes
Outdoor unit fan 1 motor error.
17 flashes
Outdoor unit fan 2 motor error.
11 flashes
Discharge temperature protection (permanent stoppage).
12 flashes
Compressor temperature protection (permanent stoppage).
20 flashes
Low pressure abnormal.
If it doesn't, if a fault has occurred on the outdoor unit
as indicated by the Hydraulic Unit, you must remove
the front (right-hand) facing from the outdoor unit.
Faults are coded by LED flashes. Error messages are
listed in the table below:
LED display on the outdoor unit
Clear
1
2
4
5
20
27
7
11
12
8
9
10
13
14
24
15
33
17
18
22
25
26
25