Diagnostics alarm
Safety-related shutoff
Channel/component tempo-
rarily unavailable
Mismatch of safety destina-
tion address (F_Dest_Add)
Safety destination address
not valid (F_Dest_Add)
Safety source address not
valid (F_Source_Add)
Safety watchdog time value
is 0 ms (F_WD_Time)
Parameter F_SIL exceeds
SIL from specific device
application
Parameter F_CRC_Length
does not match the generat-
ed values
Version of F-parameter set
incorrectly
CRC1 fault
Save iParameter watchdog
time exceeded
Restore iParameter watch-
dog time exceeded
Inconsistent iParameters
(iParCRC error)
F_Block_ID not supported
Digital output module F-DQ 8x24VDC/0.5A PP HF (6ES7136-6DC00-0CA0)
Manual, 05/2017, A5E38578424-AA
Fault
Meaning
code
25
For safety purposes, channel was
D
switched off due to an error on another
channel.
Possible causes:
A short-circuit exists.
The capacitive load is too high.
31
The firmware version of the F-module is
D
inconsistent.
64
The firmware of the F-module has de-
D
tected a different F-destination address.
65
The firmware of the F-module has de-
D
tected an illegal different F-destination
address.
66
The firmware of the F-module has de-
D
tected a different F-source address.
67
The firmware of the F-module has de-
D
tected an invalid watchdog time.
68
The firmware of the F-module has de-
D
tected a discrepancy between the SIL
setting of the communication and the
application.
69
The firmware of the F-module has de-
D
tected a discrepancy in the CRC length.
70
The firmware of the F-module has de-
D
tected an incorrect F_Par_Version or an
invalid F_Block_ID.
71
The firmware of the F-module has de-
D
tected inconsistent F-parameters.
73
iPar server does not respond to "save
D
IPar" within 4.4 minutes.
74
iPar server does not respond to "restore
D
IPar" within 4.4 minutes.
75
The firmware of the F-module has de-
D
tected inconsistent iParameters.
76
The firmware of the F-module has de-
D
tected an incorrect block ID.
Interrupts/diagnostic messages
6.3 Diagnostics alarms
Solution
Correct the process wiring.
Increase the test times (dark, light).
Repeat the firmware update.
Check the parameter assignment
of the PROFIsafe driver and the
PROFIsafe address assigned to
the F-module.
Assign the PROFIsafe address to
the F-module (again).
Check the configuration/parameter
assignment of the iPar server.
Check the configuration/parameter
assignment of the iPar server.
Check the parameter assignment.
Check the parameter assignment of
the PROFIsafe driver.
43