3582, 582i, and 3583
Table 4. Hazardous Area Classifications for Fisher 582i Converter
Certification
Body
Intrinsically Safe
Ex ia IIC T4/T5/T6 per drawing GE28591
Ex ia Intrinsically Safe
Class I, II Division 1 GP A,B,C,D,E,F,G
T4/T5/T6 per drawing GE28591
Explosion Proof
Ex d IIC T6

CSA

Class I, Division I, GP A,B,C,D T6
Type n
Ex nA IIC T6
Class I, Division 2, GP A,B,C,D T6
Class II, Division 1 GP E,F,G T6
Class II Division 2 GP F,G T6
1.These hazardous area classification also apply to 3582i positioners.
Table 5. Hazardous Area Classifications for Fisher 582i Converter
Certification
Body
Intrinsically Safe
Class I Zone 0 AEx ia IIC T4/T5/T6
per drawing GE28590
Class I, II, III Division 1 GP A,B,C,D,E,F,G
T4/T5/T6 per drawing GE28590
Explosion Proof
Class I Zone 1 AEx d IIC T6
FM
Class I, Division I, GP A,B,C,D T6
Type n
Class I Zone 2 AEx nA IIC T6
Class I Division 2, GP A,B,C,D T6
Class II Division 1, GP E,F,G T6
Class II Division 2, GP F,G T6
1.These hazardous area classification also apply to 3582i positioners.
CSA
Intrinsically Safe, Explosion proof, Type n,
Dust-Ignition proof, DIV 2
No conditions of safe use.
Refer to table 4 for additional information, figure 28
for CSA loop schematics, and figure 29 for the
CSA/FM approvals nameplate.
FM
Special Conditions of Use
Intrinsically Safe, Explosion proof, Type n,
Non-incendive, Dust-Ignition proof
No conditions of safe use.
Refer to table 4 for additional information, figure 30
for the FM loop schematic, and figure 29 for the
CSA/FM approvals nameplate.
8
Certification Obtained
Certification Obtained
Entity Rating
Temperature Code
Vmax = 30 VDC
T4 (Tamb v 71°C)
Imax = 150 mA
T5 (Tamb v 62°C)
Pi = 1.25 W
T6 (Tamb v 47°C)
Ci = 0 nF
Li = 0 mH
− − −
T6 (Tamb v 71°C)
− − −
T6 (Tamb v 71°C)
T6 (Tamb v 71°C)
− − −
(1)
Entity Rating
Temperature Code
Vmax = 30 VDC
T4 (Tamb v 71°C)
Imax = 150 mA
T5 (Tamb v 62°C)
Pi = 1.25 W
T6 (Tamb v 47°C)
Ci = 0 nF
Li = 0 mH
− − −
T6 (Tamb v 71°C)
− − −
T6 (Tamb v 71°C)
T6 (Tamb v 71°C)
− − −

ATEX

Standards Used for Certification
EN 60079−0: 2006
EN 60079−1: 2007
EN 60079−11: 2007
EN 60079−15: 2005
Special Conditions for Safe Use
Intrinsically Safe, Dust
This equipment is intrinsically safe and can be used
in potentially explosive atmospheres.
The electrical parameters of certified equipment
which can be connected to the device must not
exceed one of these following values:
Uo v 30 Vdc ; Io v 150 mA ; Po v 1.25 W
Instruction Manual
(1)
—CSA (Canada)
Enclosure Rating
CSA Type 3 Encl.
CSA Type 3 Encl.
CSA Type 3 Encl.
CSA Type 3 Encl.
—FM (United States)
Enclosure Rating
NEMA 3, IP54
NEMA 3, IP54
NEMA 3, IP54
NEMA 3, IP54
EN 61241−0: 2006
EN 61241−1: 2004
EN 61241−11: 2006