Csa - Emerson Fisher 3610J Instruction Manual

And electro-pneumatic converter
Hide thumbs Also See for Fisher 3610J:
Table of Contents

Advertisement

3610J and 3620J Positioners
September 2017
WARNING
Failure to follow these conditions of "safe use" could result in personal injury or property damage from fire or explosion,
and area re‐classification.

CSA

Intrinsically Safe, Explosion-proof, Type n, Dust‐Ignition proof, DIV 2
No special conditions for safe use.
Refer to table 4 for approval information.
Table 4. Hazardous Area Classifications for Fisher 3622 Converter
Certification Body
Intrinsically Safe
Ex ia IIC T4/T5/T6 per drawing GE28591 (see figure 31)
Ex ia Intrinsically Safety
Class I, II Division 1 GP A,B,C,D,E,F,G
T4/T5/T6 per drawing GE28591 (see figure 31)
Explosion-proof
Ex d IIC T5
CSA
Class I, Division I, GP A,B,C,D T5
Type n
Ex nA IIC T6
Class I, Division 2, GP A,B,C,D T6
Class II, Division 1, GP E,F,G T5
Class II, Division 2, GP F,G T6
1. These hazardous area classification also apply to 3620J positioners.
FM
Intrinsically Safe, Explosion-proof, Type n, Dust‐Ignition proof, Non‐incendive
No special conditions for safe use.
Refer to table 5 for approval information.
Table 5. Hazardous Area Classifications for Fisher 3622 Converter
Certification Body
Intrinsically Safe
Class 1 Zone 0 AEx ia IIC T4/T5/T6 per drawing GE28590 (see figure 32)
Class I, II, III Division 1 GP A,B,C,D,E,F,G T4/T5/T6
per drawing GE28590 (see figure 32)
Explosion-proof
Class 1 Zone 1 AEx d IIC T5
FM
Class I, Division I, GP A,B,C,D T5
Type n
CL 1 Zone 2 AEx nA IIC T5
Class I, Division 2, GP A,B,C,D T5
Class II, Division 1, GP E,F,G T5
Class II, Division 2, GP F,G T5
1. These hazardous area classification also apply to 3620J positioners.
8
Certification Obtained
Certification Obtained
(1)
—CSA (Canada)
Entity Rating
Vmax = 30 VDC
Imax = 150 mA
Pi = 1.25 W
Ci = 0 nF
Li = 0 mH
- - -
- - -
- - -
(1)
—FM (United States)
Entity Rating
Vmax = 30 VDC
Imax = 150 mA
Pi = 1.25 W
Ci = 0 nF
Li = 0 mH
- - -
- - -
- - -
Instruction Manual
D200149X012
Temperature Code
T4 (Tamb ≤ 82°C)
T5 (Tamb ≤ 62°C)
T6 (Tamb ≤ 47°C
T5 (Tamb ≤ 82°C)
T6 (Tamb ≤ 82°C)
T6 (Tamb ≤ 82°C)
T5 (Tamb ≤ 82°C)
T6 (Tamb ≤ 82°C)
Temperature Code
T4 (Tamb ≤ 82°C)
T5 (Tamb ≤ 62°C)
T6 (Tamb ≤ 47°C)
T5 (Tamb ≤ 82°C)
T5 (Tamb ≤ 82°C)
T5 (Tamb ≤ 82°C)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fisher 3620jFisher 3622

Table of Contents