Nepsi; Inmetro - Emerson Fisher 3582 Instruction Manual

Electro-pneumatic converter, and valve stem position transmitters
Hide thumbs Also See for Fisher 3582:
Table of Contents

Advertisement

3582, 582i, and 3583
Certificate
Intrinsically Safe
Gas
Ex ia IIC T4/T5/T6
IECEx
Flameproof
Gas
Ex d IIC T6
Type n
Gas
Ex nA IIC T6
1.These hazardous area classification also apply to 3582i positioners.
Certificate
Intrinsically Safe
Gas
Ex ia IIC T4/T5/T6
Dust
DIP A21 T4/T5/T6

NEPSI

Flameproof
Gas
Ex d IIC T6
Dust
DIP A21 T6
1. These hazardous area classification also apply to 3582i positioners.
Table 9. Hazardous Area Classifications for Fisher 582i Converter
Certificate
Certification Obtained
Intrinsically Safe
BR-Ex ia IIC T6/T5/T4

INMETRO

Flameproof
BR Ex d IIC T6
1. These hazardous area classification also apply to 3582i positioners.
Flameproof
Warning! DISCONNECT POWER BEFORE
OPENING
−40_C v Ta v +71_C; T6 (Ta v +71_C)
Refer to table 7 for approval information, and figure
31 for the ATEX/IECEx approvals nameplate.
Type n
Warning! DISCONNECT POWER BEFORE
OPENING
−40_C v Ta v +71_C; T6 (Ta v +71_C)
Refer to table 7 for approval information and figure
31 for the ATEX/IECEx approvals nameplate.
10
Table 7. Hazardous Area Classifications for Fisher 582i Converter
Certification Obtained
Table 8. Hazardous Area Classifications for Fisher 582i Converter
Certification Obtained
Entity Rating
Temperature Code
Ui = 30 VDC
T4 (Tamb v 71°C)
Ii = 150 mA
T5 (Tamb v 62°C)
Pi = 1.25 W
T6 (Tamb v 47°C)
Ci = 0 nF
Li = 0 mH
− − −
T6 (Tamb v 71°C)
T6 (Tamb v 71°C)
− − −
Entity Rating
Temperature Code
Ui = 30 VDC
T4 (Tamb v 71°C)
Ii = 150 mA
T5 (Tamb v 62°C)
Pi = 1.25 W
T6 (Tamb v 47°C)
Ci = 0 nF
Li = 0 mH
T6 (Tamb v 71°C)
− − −
Entity Rating
Temperature Code
Ui = 60 V Ii= 150 mA
T4 (−20°C to 80°C)
Ui = 60 V Ii= 150 mA
T5 (−20°C to 50°C)
Ui = 60 V Ii= 120 mA
T6 (−20°C to 50°C)
− − −
T6 (−20°C to 50°C)
NEPSI
Special Conditions of "Safe Use"
Intrinsically Safe, Dust & Flameproof, Dust
Refer to table 8 for approval information.
Contact your Emerson Process Management sales
office for additional "safe use" information.
INMETRO
Special Conditions of "Safe Use"
Intrinsically Safe, Flameproof
Refer to table 9 for approval information and figure
32 for the INMETRO approval nameplates.
Contact your Emerson Process Management sales
office for additional "safe use" information.
Instruction Manual
(1)
—IECEx
Enclosure Rating
IP54
IP54
IP54
(1)
—NEPSI
Enclosure Rating
IP64
IP64
(1)
—INMETRO
Enclosure Rating
− − −
− − −
June 2010

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fisher 582iFisher 3583