3582, 582i, and 3583

Loop Schematics/Nameplates

This section includes loop schematics required for wiring of intrinsically safe installations. It also contains the
approvals nameplates. If you have any questions, contact your Emerson Process Management sales office.
NOTES:
1. BARRIERS MUST BE CSA CERTIFIED WITH ENTITY PARAMETERS
AND ARE TO BE INSTALLED IN ACCORDANCE WITH THE
MANUFACTURER'S I.S. INSTALLATION INSTRUCTIONS.
2. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE
CANADIAN ELECTRICAL CODE, PART I.
3. FOR ENTITY INSTALLATION (I.S. AND N.I.): Vmax > Voc, Imax > Isc,
Ci + Ccable < Ca, Li + Lcable < La.
GE28591 Rev A
46
Figure 28. CSA Loop Schematic for Fisher 582i Converter
Figure 29. CSA / FM Approvals Nameplate for Fisher 582i Converter