Clearances To Combustibles As A Built-In, Ul And Ulc - Quadra-Fire PELLET INSERT CB1200I Owner's Manual

Pellet insert installation and operation
Hide thumbs Also See for PELLET INSERT CB1200I:
Table of Contents

Advertisement

R
R R
B. Clearance To Combustibles, UL and ULC
Figure 9.1
A
B
C
D
INSTALLED AS A BUILT-IN UNIT
Shown with Rear Vent and Optional Outside Air
Combustible
Mantel
12 in.
(305mm)
Figure 9.2
February 3, 2010
Rear Shroud Kit is Required for Built-In Installation
A
C
0 INCH (0mm) CLEARANCE TO ExPOSED SECTION AND FACE TRIM
Top of Shroud
Sides of Inside Shroud
Back of Inside Shroud
Vent Pipe to Combustible
Shown with Hopper Extended
Rear Shroud
AS A BUILT-IN
B
Top Vent
Rear Vent
Top or Rear Vent
Top Vent
Rear Vent
Top or Rear Vent
NOTICE:
Please note that while the minimum clear-
ance for the termination cap is 6 inches
(152mm) there is the possibly of soot
buildup around the termination area. If this
occurs we suggest to move the termination
further away from the house to prevent it.
6 in.
(152mm)
NOTE:
Optional Outside
Air
7014-188B
CB1200-I Pellet Insert
D
C
B
E
3.0
76
0
0
0
0
2.5
64
0
0
3.0
76
WARNING
Fire Risk.
Comply with all minimum clear-
ances to combustibles as specified.
Failure to comply may cause house fire.
Illustrations reflect typical installations and
are FOR DESIGN PURPOSES ONLY.
Illustrations/diagrams are not drawn to
scale.
Actual installation may vary due to
individual design preference.
Page 9