Victaulic Gasket Installation

1. Inspect supplied gasket to be certain it is suited for
intended service (code identifies gasket grade). Apply
a thin coat of silicone lubricant to gasket tips and
outside of gasket.
2. Install gasket, placing gasket over pipe end and making
sure gasket lip does not overhang pipe end. Refer to
Figure 18
for gasket configuration.
Table 6.
Installation data for 150 psig flange adapters (Style 741)
Assembly Bolt
Nominal Pipe Size
in.
mm
4
114.3
5
141.3
6
168.3
8
219.1
10
273.0
12
323.9
14
355.6
16
406.4
(a) Bolt size for conventional flange to flange connection. Longer bolts are required when flange washer must be used.
Table 7.
Installation data for 350 psig flange adapters (Style 743)
Assembly Bolt
Nominal Pipe Size
in.
mm
4
114.3
5
141.3
6
168.3
8
219.1
10
273.0
12
323.9
(a) Bolt size for conventional flange to flange connection. Longer bolts are required when flange washer must be used.
CVHE-SVX02H-EN
Number of
(a)
Size
Assembly Bolts
in.
Required
5/8 x 3
8
3/4 x 3-1/2
8
3/4 x 3-1/2
8
3/4 x 3-1/2
8
7/8 x
12
7/8 x 1/4
12
1 x 4-1/2
12
1 x 4-1/2
16
Number of
(a)
Size
Assembly Bolts
in.
Required
3/4 x 3-3/4
8
3/4 x 4
8
3/4 x 4-1/2
12
3/4 x 4-3/4
12
1 x 5-1/4
16
1-1/8 x 5-3/4
16
Figure 18. Typical Victaulic flange gasket configuration
3. Align and bring two pipe ends together and slide
gasket into position centered between the grooves on
each pipe. No portion of the gasket should extend into
the groove on either pipe.
4. Open fully and place hinged Victaulic flange around
the grooved pipe end with the circular key section
locating into the groove.
5. Insert a standard bolt through the mating holes of the
Victaulic flange to secure the flange firmly in the
groove.
6. Tighten fasteners alternately and equally until housing
bolt pads are firmly together (metal to metal); refer to
"Bolt-Tightening Sequence for Water Piping
Connections, " p.
28. Do not excessively tighten
fasteners.
Note: Uneven tightening may cause gasket to pinch.
Bolt Pattern Diameter
in.
mm
7.5
191
8.5
216
9.5
241
11.75
298
14.25
362
17
432
18.75
476
21.25
540
Bolt Pattern Diameter
in.
mm
7.88
200
9.25
235
10.63
270
13
330
15.25
387
17.75
451
Installation: Water Piping
Weight
lb
kg
7.7
3.5
9.3
4.2
10.3
4.7
16.6
7.5
24.2
11.0
46.8
21.2
75
34.0
90
40.8
Weight
lb
kg
15.3
6.9
17.7
8.0
23.4
10.6
34.3
15.6
48.3
21.9
70.5
32.0