Fig. 2.6.4 Digital Outputs Connection - Honeywell IPC5000 Installation Manual

Universal programmable controller
Table of Contents

Advertisement

4) Connection of Digital outputs
1
DO_COM1
DO1
2
DO2
3
4
DO3
5
DO4
DO5
6
DO6
7
8
DO_COM2
9
DO7
DO8
10
DO9
11
DO10
12
DO11
13
DO12
14
Fig. 2.7.4 Digital outputs Connection
CAUTION
Open-collector output of IPC5000 is designed for 30VDC and less than 100mA. When
using a relay as a load, use a relay for 24VDC. 24 volt power supply needs supplied by
user. Supply should have a minimum current rating of 1.5A.