Honeywell IPC5000 Installation Manual page 97

Universal programmable controller
Table of Contents

Advertisement

Program specifications
Items
No. of programs
No. of segments
Segment setting system
PID group setting
WAIT function
(Guarantee Soak)
Repeat
Program section
PV Start
Event setup
Program link
Program name
POWER FAILURE
Specification
100 programs (0 ~ 99)
100 segments/1 program, or total 2000 segments
Segment time: Set by set points (SP) and time
(Max. 99hours59min or 99min59sec)
Segment Ramp-unit:
Soaking-segment ramp rate (hr.min/min.sec)
Ascending/descending ramp (Slope per hour/min)
* Time unit is switchable
Using segment PID
Using zone PID: According to PV
According to SP
Group No.: 1 to 8
Type (Front, rear, all) and WAIT zone and WAIT time
1 pattern all repeat x 1 (Maximum repeat is 999 cycle)
Part repeat x 5 (Maximum repeat is 999 cycle)
Starting Target Set Point (SSP1 or SSP2)
Starting with PV data point: Program operation starts with the
PV data at the time of starting and advances toward the target
Set Point of segment-1 for both PV1 and PV2 programs
TIME and PV events setup are available. Max 2000 items.
Maximum 6 programs
Link program registration: Maximum 10 links
100 programs (Each pattern can have its name), Max. 12
characters
Controls right away after recovery of power failure, if the power
failure lasts less than 5 seconds.
For power failure that lasts longer than 5 seconds, setup
modes below will be followed.
BREAK: Stops program
HOT START: Controls at the state just before power failure
COLD START: It starts again at the beginning of program
(Note) It is HOT START for fix control
- 87 -