How To Remove The Plate Heat Exchanger - Mitsubishi Electric EHSE-YM9EC Service Manual

Hydrobox
Table of Contents

Advertisement

DISASSEMBLY PROCEDURE

9. How to remove the plate heat exchanger

(1) P ump down the refrigerant circuit and close the stop
valve on the outdoor unit. (Refer to "12. Supplementary
information".)
(2) Remove the front panel. (Refer to Procedure 1.)
(3) R emove the water pump and the pump valve. (Refer to
Procedure 5.)
(4) R emove the Joint (WC-PUMP) by removing the 2
screws, and detaching the different diameter quick
connection. (Photo 9-2)
• When reinstalling the different diameter quick connection,
use a new O-ring.
• R efer to page 70 for how to attach and detach the
different diameter quick connection.
Photo 9-2
Screws
Water coil cover
Nut (G1-1/2")
Screw
Water pump
Nut (G1-1/2")
Pump valve
Screw
Plate heat exchanger
(inside)
O-ring
Screws
OCH590B
Joint
Different diameter
(W.C.-W.P.)
O-ring
quick connection
Different diameter
quick connection
64
PHOTOS
Photo 9-1
Water pump
connector (CNP1)
Earth cable
Lead
wire
Cable strap
Screws
CNPWM
connector
Cable
clamps
Booster heater
Pipe
(P.V.-B.H.)
Different diameter
quick connection
O-ring
Strainer valve
Same diameter
quick connection
O-ring

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents