No.
Fault symptom
26 Cooling mode is NOT
DIP SW2-4 is OFF.
available.
27 The cooling system
1.
When the water in the circulation circuit is
unduly hot, Cooling mode starts with a delay
does not cool down to
for the protection of the outdoor unit.
the set temperature.
2.
When the outdoor ambient temperature is
lower than the preset temperature that acti-
vates the freeze stat. function, Cooling mode
does not start running.
28 The electric heaters
The setting time period of Heat-pump-only opera-
tion is short.
are activated shortly
after DHW or LP
mode starts running
after Cooling mode.
29 During DHW or LP
The unit runs in Cooling mode when the outdoor
ambient temperature is lower than 10ºC (outside
mode following the
of the guaranteed operating range).
cooling mode, error
(When defrosting operation is running at such a
L6 (circulation water
low outdoor ambient temperature after Cooling
freeze protection
mode is switched to DHW or LP mode, the water
error ) occurs and the
temperature in the cooling circuit drops too low,
system stops all the
which could result in L6 error to stop all the opera-
operations.
tions.
30 The energy monitor
1. Incorrect setting of the energy monitor
value seems not cor-
rect.
2. N on-connectable type of external meter (local
supply) is connected.
3. E xternal meter (local supply) failure
4. FTC board failure

Annual Maintenance

It is essential that the hydrobox is serviced at least once a year by a qualified individual any spare parts required MUST be purchased from Mitsubishi Electric (safety
matter).
NEVER bypass safety devices or operate the unit without them being fully operational.
<Draining the hydrobox>
WARNING: DRAINED WATER MAY BE VERY HOT
1. Before attempting to drain the hydrobox isolate from the electrical supply to prevent booster heater burning out.
2. Isolate hydrobox from primary water circuit and drain water from hydrobox. Use a suitable heat resistant hose to assist in these operations.
3. Drain any remaining water from booster heater using fitted drain cock and hose to safely drain the unit.
4. After the hydrobox is drained, water remains in the following component parts. Drain water completely by checking the inside of the parts.
• Strainer (Remove the strainer cover.)
• Pressure relief valve (Operate the valve.)
<Annual maintenance points>
Use the Annual Maintenance Log Book (in 13-2.) as a guide to carrying out the necessary checks on the hydrobox and outdoor unit.
OCH590B
Possible cause
Explanation - Solution
Turn DIP SW2-4 to ON. (Refer to "6-5. DIP switch settings".)
1.
Normal operation
2.
To run Cooling mode overriding the freeze stat. function, adjust the preset
temperature that activates the freeze stat. function.
(Refer to "Freeze stat function" in "9-4. Service Menu" on Page 28.)
Adjust the setting time period of Heat-pump only operation. (Refer to "Electric
heater (DHW) in "9-4. Service Menu" on Page 26.
Do not run Cooling operation when the outdoor ambient temperature is lower
than 10ºC.
To automatically stop or recover only Cooling operation and keep other opera-
tions running, the freeze stat. function can be used. Set the preset temperature
that activates the freeze stat. function to adjust the outdoor ambient temperature
as follows. (Refer to "Freeze stat function" in "9-4. Service Menu" on Page 28.)
Outdoor ambient temperature
3ºC higher than the preset temperature
5ºC higher than the preset temperature
1. Check the setting by following the procedure below.
(1) Check if the DIP switch is set as the table below.
Consumed electric energy
Electric energy meter
SW3-4
(Local supply)
OFF
Without
ON
With
(2) I n the case external electric energy meter and/or heat meter is not used,
check if the setting for electric heater and water pump(s) input is correct by
referring to <Energy monitor setting> in "9-4. Service Menu".
(3) I n the case external electric energy meter and/or heat meter is used, check if
the unit of output pulse on external meter matches with the one set at the
main remote controller by referring to <Energy monitor setting> in "9-4.
Service Menu".
2. C heck if the external meter (local supply) is connectable type by referring to
<Energy monitor setting>" in "9-4. Service Menu".
3. C heck if signal is sent to IN8 to IN10 properly. (Refer to "6. WIRING DIAGRAM")
Replace the external heat meter if defective.
4. Check the FTC control board.
• Check for faulty wiring.
• I f no problem found with the wiring, the FTC control board is faulty. Replace the
board.
52
Cooling operation
Stop
Recover
Delivered heat energy
Heat meter
SW3-8
(Local supply)
OFF
Without
ON
With