Reversing Amplifier For Double-Acting Actuators - Samson 3730-6 Mounting And Operating Instructions

3730 series electropneumatic positioner with hart communication and pressure sensors
Table of Contents

Advertisement

Attachment to the control valve – Mounting parts and accessories
4.5
Reversing amplifier for
double-acting actuators
For the use with double-acting actuators, the
positioner must be fitted with a reversing
amplifier, e.g. the SAMSON Type 3710 Re-
versing Amplifier (see Mounting and Oper-
ating Instructions EB 8392 EN).
4.6
Attaching an external
position sensor
Refer to Table 7 on page 44 for the required
mounting parts and accessories.
In the positioner version with an external po-
sition sensor, the sensor placed in a sepa-
rate housing is attached over a plate or
bracket to the control valve. The travel
pick-off corresponds to that of a standard
device.
The positioner unit can be mounted as re-
quired to a wall or a pipe.
Fig. 12 · Positioner unit with sensor mounted on a
micro-flow valve
For the pneumatic connection either a con-
necting plate (6) or a pressure gauge
bracket (7) must be fixed to the housing, de-
pending on the accessories chosen. Make
sure the seal rings (6.1) are correctly in-
serted (see Fig. 6 on page 27, bottom right).
34
EB 8384-6 EN
For the electrical connection a 10 meter
connecting lead with M12x1 connectors is
included in the scope of delivery.
Note:
– In addition, the instructions in sections
5.1 and 5.2 apply for the pneumatic and
electrical connection.
Operation and setting are described in
sections 7 and 8.
– Since 2009, the back of the position sen-
sor (20) is fitted with two pins acting as
mechanical stops for the lever (1). If this
position sensor is mounted using old
mounting parts, two corresponding
Ø 8 mm holes must be drilled into the
mounting plate/bracket (21).
4.6.1 Mounting the position sen-
sor with direct attachment
Type 3277-5 Actuator with 120 cm²
The signal pressure from the positioner is
routed over the signal pressure connection
of the connecting plate (9, Fig. 13 left) to the
actuator diaphragm chamber. To proceed,
first screw the connecting plate (9) included
in the accessories onto the actuator yoke.
4
Turn the connecting plate (9) so that the
correct symbol for the fail-safe position
"Actuator stem extends" or "Actuator
stem retracts" is aligned with the marking
(Fig. 13, below).
4
Make sure that the gasket for the con-
necting plate (9) is correctly inserted.
4
The connecting plate has boreholes with
NPT and G threads.
Seal the threaded connection that is not
used with the rubber seal and square plug.

Advertisement

Table of Contents
loading

Table of Contents