6.6 Touch Panel Configuration

The Touchscreen can be configured to match local preferences and it can be recalibrated if it does not perform as
expected.
6.6.1 How to Change the Backlight Timeout and Brightness
1)
Login as Administrator or Service.
2)
Touch the
Menu>Configuration>Display
3)
Touch and enter LCD Backlight Timeout and Brightness settings, or touch [Start] to calibrate the Touch Panel (see
below).
4)
Touch [Finish] and return to the Configuration menu.
Parameter Name
Default Setting
Backlight time out
6.6.2 How to Calibrate the Touch Panel
To calibrate the screen:
1)
Login as Administrator or Service.
2)
Touch
Menu>Configuration>Display
3)
Touch [Start].
4)
Follow the instructions on screen, touching each marker as it appears.
5)
Touch [Finish] and return to the Configuration menu.
6.7 Latching Alarms
Latched alarms stay active (after the input reading has reverted to the normal range) until acknowledged, whereas
Unlatched alarms are automatically reset when the reading goes back to the normal range.
To set or change latched alarms:
1)
Log in as Service.
2)
Touch
Menu>Configuration>Channel Settings
3)
Touch the Input Module to change (circled)...:
MAN0984_Iss 3_02/16
Pt. No. 3011M5001_3
Commissioning
Value Range
30 seconds
0.5 to 10 mins
(0.5 min)
or
Always On
.
This is the time that the backlight will remain on after the
Touchscreen is idle.
If a new event occurs, the backlight will come on and will
remain on as long as the event remains unacknowledged.
.
.
52
Comment
Touchpoint Plus
Technical Handbook

Hide quick links:

Advertisement

Table of Contents