Rectification and Modification
6)
Replace the battery pack with Honeywell Analytics Part No. TPPLSIBB.
7)
Reconnect the battery connector to the PCB.
8)
Switch the backup battery On/Off switch back to On.
9)
Close the enclosure door and secure the handle with the two security screws.
10) Switch power on and restore TPPL to normal operation.
11) Touch the power icon to check battery power levels.
Note: Ensure that the battery On/Off switch is in the On position before closing the access door or the backup battery will
not work when it is most required.

10.8 Return to Factory Default Settings

If required, the system Administrator or a Honeywell Service Technician can return the TPPL Controller to its Factory
Default settings. This may be required to fix a fault or as part of a major system update.
Passwords are not changed when resetting to Factory Default settings so this procedure cannot be used to restore
forgotten passwords to the default password.
Returning TPPL to its Factory Default settings will initialize all user settings e.g. mA and mV Input channel
Your TPPL system may become inoperative until it is reconfigured correctly (see Ch. 6 Commissioning), and you
should put alternative safety arrangements in place until the system is returned to normal operation.
10.8.1 To Reset the Touchpoint Plus to its Factory Default Settings
1)
Log in as Administrator.
2)
Touch
Maintenance>Service Mode>Reset to Default>Yes
3)
If required, recommission and reconfigure the Touchpoint Plus system (Ch. 6 Commissioning).
4)
Log out.
MAN0984_Iss 3_02/16
Pt. No. 3011M5001_3
Figure 53. Battery On/Off Switch and Battery Connector