Installing the Cisco MDS 9132T Switch
1
2
3
To install the shelf brackets in an EIA rack, follow these steps:
Step 1
Position a shelf bracket inside the rack-mounting posts as shown in the above figure. Align the screw holes at the front
of the shelf bracket with the holes in the front rack-mounting post. Then attach the shelf bracket to the front rack-mounting
post using a minimum of four 12-24 or 10-24 screws.
Note
The bottom hole of the shelf bracket should align with the bottom hole of a rack unit on the rack-mounting post
(the hole immediately above the 1/2 in. spacing).
Step 2
Repeat with the other shelf bracket.
Step 3
Verify that the shelf brackets are at the same height (using the level or tape measure as desired).
Step 4
Attach the crossbar to the shelf brackets as shown in the above figure, using the 10-32 screws.
Step 5
Insert the slider posts into the shelf brackets as shown in the above figure. Attach them to the rear rack-mounting posts
using a minimum of four 12-24 or 10-24 screws.

Preinstalling the Switch

Airflow Considerations
The switch comes with fan and power supply modules that have either port-side intake or port-side exhaust
airflow for cooling the switch. If you are positioning the port end of the switch in a cold aisle, make sure that
the switch has port-side intake fan and power supply modules with red colorings. If you are positioning the
fan and power supply modules in a cold aisle, make sure that the switch has port-side exhaust fan and power
supply modules with blue colorings. All fan and power supply modules must have the same direction of
airflow.
Connection Guidelines for AC-Powered Systems
For connecting the Cisco MDS 9132T switch AC power supplies to the site power source, follow these basic
guidelines:
• Each power supply should have its own dedicated branch circuit.
• Circuits should be sized according to local and national codes.
• The AC power receptacles used to plug in the chassis must be the grounding type. The grounding
Rack-mounting post
Shelf bracket
Slider post
conductors that connect to the receptacles should connect to protective earth ground at the service
equipment.
4
Crossbar
5
10-32 screws
Cisco MDS 9132T Fibre Channel Switch Hardware Installation Guide
Preinstalling the Switch