Maintenance Checklist - Roberts Gorden CoRayVac CRT-10 Installation, Operation & Service Manual

Custom-engineered, low-intensity infrared heating systems
Hide thumbs Also See for CoRayVac CRT-10:
Table of Contents

Advertisement

CORAYVAC
®
I
NSTALLATION
Withdraw the connection block. Remove the ground
wire from the gas valve and from the air shutter
screw. The gas train can now be withdrawn from the
compartment. The gas train can now be dismantled.
Replace part and reassemble in reverse order.
NOTE: When reassembling, a suitable sealant must
be used to ensure that no gas leaks occur. Further
to this, the assembly must be square so that all the
components are upright.
13.2.5 Automatic Flame Control Unit
Remove ignition lead, sense wire and other connec-
tors. Unscrew two screws from the cover. Replace if
faulty. Refit in reverse sequence.
13.2.6 Neons
Remove the two push connectors from the neon.
Remove the neons by depressing the retaining tabs
inward. Replace in reverse sequence.
The Vicinity of the Heater Do not store or use flammable objects, liquids or vapours near the heating
Vehicles and Other
Objects
Reflector
Vent Pipe
Outside Air Inlet
44 of 54
O
S
M
PERATION AND
ERVICE
ANUAL
system. Immediately remove these items if they are present.
See Page 5, Section 3.
Maintain the clearances to combustibles.
Do not hang anything from, or place anything on, the heater.
Make sure nothing is lodged underneath the reflector, in between the tubes
or in the decorative or protective grilles (included with select models).
Immediately remove objects in violation of the clearances to combustibles.
See Page 5, Section 3.
Support reflector with reflector hanger and support strap.
Reflector must not touch tube.
Make sure there is no dirt, sagging, cracking or distortion.
Do not operate if there is sagging, cracking or distortion.
Make sure reflectors are correctly overlapped. See Page 18, Section 6.4.3.
Clean outside surface with a damp cloth.
Venting must be intact. Using a flashlight, look for obstructions, cracks on
the pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and dust.
Remove any carbon deposits or scale using a wire brush.
Inlet must be intact. Look for obstructions, cracks on the pipe, gaps in the
sealed areas or corrosion.
The area must be free of dirt and dust. Clean and reinstall as required.

13.3 Maintenance Checklist

Installation Code and Annual Inspections:
All installation and service of ROBERTS GORDON
equipment must be performed by a contractor quali-
fied in the installation and service of equipment sold
and supplied by Roberts-Gordon Europe Limited
and conform to all requirements set forth in the
ROBERTS GORDON
®
governmental authorities pertaining to the installa-
tion, service and operation of the equipment.
To help facilitate optimum performance and safety,
Roberts-Gordon Europe Limited recommends that a
qualified contractor conduct, at a minimum, annual
inspections of your ROBERTS GORDON
ment and perform service where necessary, using
only replacement parts sold and supplied by Rob-
erts-Gordon Europe Limited.
manuals and all applicable
®
equip-
®