CORAYVAC
®
I
NSTALLATION

8.5 Condensate Drain Assembly

The condensate drain assembly is composed of a
tee, draincap, and a non return valve.
A condensate drain assembly must be installed on the
inlet side of the pump assembly if there is horizontal
venting of the pump, See Figure 19.
A seperate condensate drain on the pump discharge
side is required if there is vertical venting of the
pump or if there is a vertical rise in the discharge line
away from the pump. See Page 33, Figure 20.

Figure 19: Condensate Drain Assembly - Horizontal Flue

Drain Cap
1" BSP threaded hole.
Use 1" x ¾" reducer.
(not supplied)
3/4" CPVC Pipe
100 mm minimum
vertical drop
between pump
and non-return
valve.
Description
Tee 100 mm (4")
Tee 150 mm (6")
Drain Cap 100 mm (4")
Drain Cap 150 mm (6")
Non-Return Valve
Part Number
01330203
Tee, 4" (100 mm) Aluminized
01330204
Tee, 6" (150 mm) Aluminized
01331900
Damper Coupling, 4" (100 mm)
01335801
Elbow, 4" (100 mm) Aluminized 90°
02718851
Drain Cap, 4" (100 mm)
02718852
Drain Cap Assembly, 6" (150 mm)
90502300
Vent Cap, 4" (100 mm) Metalbestos
90502302
Vent Cap, 6" (150 mm) Metalbestos
T0100320
Elbow, 6" (150 mm) Aluminized 90°
32 of 54
O
S
M
PERATION AND
ERVICE
ANUAL
Tee
Pump
Inlet
Part Number
01330203
01330204
02718851
02718852
C2383B
Description
The condensate drain assembly in the pump
discharge line can be eliminated if the discharge line
is horizontal through the wall and pitched down at
least 6 mm per 3048 mm. This arrangement will per-
mit drainage of condensate through the pump and
outside via the horizontal (pitched) discharge line.
Wall
Must be connected
to a drain system
in accordance with
local codes.
Part Number
91409403
Tube, Aluminized 4" (100 mm) dia. 10' (3 m)
91409420
Tube, Aluminized 6" (150 mm) dia. 10' (3 m)
91412800
Flexible Boot, 4" (100 mm)
91412801
4 - Flexible Boot, 1/2" (13 mm)
91412802
Flexible Boot, 6" (150 mm)
91901300
Boot Clamp, 4" (100 mm)
91913703
Boot Clamp, 6" (150 mm)
E0009356
Damper Coupling, 6" (150 mm)
3/4" female
Non-Return
Valve
3/4" CPVC
Pipe
Description
flow

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents