Vitocrossal 200, CM2 400, 500, 620 and 620 TX Service
Burner Control
(continued)
Burner Control Coding Card
4. Remove coding card from burner control sub-base
and set aside.
Note: Ensure there is no power to the burner control
when replacing the coding card.
5. Loosen the four screws from the burner control
sub-base.
6. Remove burner control sub-base.
7. Reinstall in reverse order.
1. Loosen the two programming unit screws.
2. Lift the programming unit off the burner control
sub-base and disconnect the cable plug and set aside.
3. Remove the coding card from burner control sub-base
and replace.
Note: Ensure there is no power to the burner control
when replacing the coding card.
Note: If error code "FB7"appears
check the coding card that it matches the
burner control.
4. Reinstall in reverse order.
Burner Service