Manual Operation Of A Modulating Burner; Manual Operation Of A 2-Stage Burner - Siemens RWF40.000A97 User Manual

Rwf40 series, compact universal controllers
Hide thumbs Also See for RWF40.000A97:
Table of Contents

Advertisement

6.2.2 Manual operation, modulating burner
Floating controller
Modulating controller
Thermostat mode
6.2.3 Manual operation, 2-stage burner
HVAC Products
‫ ٭‬Press
EXIT
for 5 seconds
The LED above the hand symbol will light up.
‫ ٭‬Change the position of the actuating device with
Relay 2 opens the actuating device as long as
Relay 3 closes the actuating device as long as
The LEDs for the actuating device indicate if «OPEN» or «CLOSE» is activated.
‫ ٭‬Change the position of the actuating device with
The analog output delivers the position of the actuating device that was entered.
‫ ٭‬Return to automatic operation by pressing
F
When manual operation is activated, the position of the actuating device will
be set to 0 until another entry with the buttons is made.
Manual operation can only be activated if the thermostat function has set relay 1 active.
If the thermostat function sets relay 1 inactive during manual operation, manual
operation is terminated.
‫ ٭‬Press
EXIT
for 5 seconds
=
‫ ٭‬Press
briefly
- Relay 2 is active, relay 3 is inactive
- Analog output (optional) delivers DC 10 V
The actuating device opens.
>
‫ ٭‬Or press
briefly
- Relay 2 is inactive, relay 3 is active
- Analog output (optional) delivers DC 0 V
The actuating device closes.
‫ ٭‬Return to automatic operation by pressing
F
If the thermostat function sets relay 1 inactive during manual operation,
manual operation is terminated.
CC1B7865en
=
>
and
=
is kept depressed.
>
is kept depressed.
=
>
and
EXIT
for 5 seconds
EXIT
for 5 seconds
05.12.2002
6. Operation