6.2.2 Manual operation, modulating burner
Floating controller
Modulating controller
Thermostat mode
6.2.3 Manual operation, 2-stage burner
HVAC Products
٭Press
EXIT
for 5 seconds
The LED above the hand symbol will light up.
٭Change the position of the actuating device with
Relay 2 opens the actuating device as long as
Relay 3 closes the actuating device as long as
The LEDs for the actuating device indicate if «OPEN» or «CLOSE» is activated.
٭Change the position of the actuating device with
The analog output delivers the position of the actuating device that was entered.
٭Return to automatic operation by pressing
F
When manual operation is activated, the position of the actuating device will
be set to 0 until another entry with the buttons is made.
Manual operation can only be activated if the thermostat function has set relay 1 active.
If the thermostat function sets relay 1 inactive during manual operation, manual
operation is terminated.
٭Press
EXIT
for 5 seconds
=
٭Press
briefly
- Relay 2 is active, relay 3 is inactive
- Analog output (optional) delivers DC 10 V
The actuating device opens.
>
٭Or press
briefly
- Relay 2 is inactive, relay 3 is active
- Analog output (optional) delivers DC 0 V
The actuating device closes.
٭Return to automatic operation by pressing
F
If the thermostat function sets relay 1 inactive during manual operation,
manual operation is terminated.
CC1B7865en
=
>
and
=
is kept depressed.
>
is kept depressed.
=
>
and
EXIT
for 5 seconds
EXIT
for 5 seconds
05.12.2002
6. Operation
33/57