5.6 Response threshold «Q»
HVAC Products
The response threshold «Q» defines for how long and how low the actual value is
allowed to drop before the system switches to high-fire operation.
An internal mathematical calculation using an integration function determines the sum of
all the areas Q
= Q1 + Q2 + Q3, as shown in the diagram. This only takes place when
eff
the control deviation (x-w) falls below the value of the switching threshold «HYS1». If
the actual value increases, integration is stopped.
If «Q
» exceeds the preset response threshold «Q» (can be adjusted on the parameter
eff
level), this causes the second stage of the burner to switch on or - in the case of a
floating controller / modulating controller – the actuating device to open.
If the actual boiler temperature reaches the required setpoint, Q
Temperature (°C)
x
w
HYS1
Q
7865d19e/1199
Monitoring of the actual value ensures that the switching frequency is kept low in the
transitional range from low- to high-fire operation, aimed at reducing wear.
CC1B7865en
Q
1
2
05.12.2002
5. Operating modes
is reset to 0 .
eff
Q
3
Q = 0
eff
t
27/57