Siemens 3VA1 100 A Manual page 193

Molded case circuit breakers
Hide thumbs Also See for 3VA1 100 A:
Table of Contents

Advertisement

Terminal cover, extended terminal cover and broadened terminal cover
All terminal covers afford degree of protection IP40 at the front of the breaker and degree of
protection IP20 at the infeed and load ends provided that they are correctly installed (cutting
of grille structure).
All terminal covers have a marking on the inside face which can be drilled through before the
cover is installed. A voltage detector can be inserted through this bore to test for safe
isolation.
Reduced degree of protection
If a hole is drilled through the terminal cover, degree of protection IP40 is no longer
afforded.
Suitable precautions must be taken to safeguard against any hazards posed by this loss of
protection.
Phase barriers can also be installed on all terminal covers in order to maintain the required
clearances and creepage distances which might be reduced as a result of ionized gas
following a short circuit.
3VA molded case circuit breakers
Manual, 04/2015, A5E03603177010-02
WARNING
Marking for bores
Accessories
4.3 Connection system
193