Neutral conductor protection N:
The neutral conductor protection function is available only for 3-pole molded case circuit
breakers with external current transformer for N conductor for 4-pole molded case circuit
breakers.
•
3VA molded case circuit breakers
Manual, 04/2015, A5E03603177010-02
3.1 Line protection applications of 3VA molded case circuit breakers
I
adjustable in steps of 1 A
N
3-pole breakers with external current transformer for N conductor:
I
< 63 A: 0.4 to 1.6 x I
n
I
≥ 63 A: 0.2 to 1.6 I
n
4-pole breakers:
I
< 63 A: 0.4 to 1.6 x I
n
I
≥ 63 A: 0.2 to 1.0 or 1.6 x I
n
n
n
n
n
Applications
123