General notes
The installation must be carried out by a
licensed electrical contractor. Observe
the regulations of the relevant authorities
and the local regulations of the power
supply company.
The power supply terminals are 'live'
even when the ON/OFF switch has been
switched OFF.
Terminal box
The control, regulating and safety equipment are fully
wired and tested.
You only need to connect the power supply and the
external accessories.
Power supply connection
Connect the power supply permanently or with a safety
plug (no plug connection in protective areas 1 and 2, i.e.
near a bath or shower).
Provide the power supply via a mains isolator (e.g. fuse,
heating system emergency stop), which ensures at least
3 mm contact separation for all poles.
Connection cable flexible, 3 x 1.0 mm² or rigid,
max. 3 x 1.5 mm².
The plug must be accessible when using a power supply
cable with safety plug. Flexible power supply cable
3 x 1.0 mm².
14

Electrical connection

CGU-2(K) / CGG-2(K)
Terminal box
3062347_0309