Safety precautions
CAUTION SIGNS
Read the installation manual thoroughly before installing the product.
Make sure to transport the product with its packages on. In case if you must remove the packaging, use soft materials to carry
the product to prevent any damages on the product.
Perform the drainage/piping work securely according to the installation manual.
If not, water could drop from the unit and household goods could get wet and damaged.
Wear thick gloves during the installation process.
If not, personal injury may occur due to the air conditioner parts.
If the DVM Hydro unit / Hydro unit HT is installed in a small area, beware of oxygen deficiency in the area that may caused by
refrigerant leakage.
Do not install or operate DVM Hydro unit / Hydro unit HT in following places:
Place where surrounding air contains mineral oil or where oil vapor occurs; or cooking area where vapor or water
particles occur by spraying. (When particles of oil sticks to the heat exchanger following incidents may occur; it may
cause performance decrease or cause condensation water to scatter. Also, if oil particles sticks to the plastic parts, it may
cause damage or deformation of those part which may lead to product malfunction or refrigerant leakage.)
Place where corrosive gas, such as sulphurous gas, exists. (When installing the product in these places, contact an
installation specialty store since the copper pipe and brazing part will need additional corrosion proof or anti-rust
additive to prevent corrosion.
Place where product is exposed to flammable gases, carbon fiber, flammable powder/dust or place where volatile
flammable gases such as thinner or gasoline is frequently used. (Gases near DVM Hydro unit / Hydro unit HT may ignite.)
Place where electromagnetic waves are emitted (Control devices may not work.)
Place with high level of basicity within the air such as near ocean; place with high voltage fluctuation such as factory; and
within the car or ship.
Place where special spray is frequently used.
Place where fine powder is used (such as bakery)
Do not use the product to store precision instrument, food, plants or animals, cosmetic goods, art works or any other
special purpose. (There is risk of property loss.)
Place where noise or vibration may occur.
After completing the installation, run the trial operation. If no error occurs, explain to the customer how to use and clean the
air conditioner according to the user's manual. In addition give the installation manual and the user's manual to the customer.
Before the installation, check if the product is in good shape.
Do not install the product with the damage which occurred during shipment.
All of the materials used to manufacture product and packages are eco-friendly and they are recyclable.
Refrigerant used in this product must be added or disposed in an appropriate way by qualified personnel.
At the end of the life cycle, take it to a proper recycling or disposal center or return it to the dealer so that it can be
disposed correctly.
Combination rate
This product should be connected with indoor unit and outdoor unit of the DVM S
The combinations of the installation.
- This product should be combined among 50~130% of outdoor unit's capacity.
- When this product would be combined with heat pump outdoor units for 180% combination rate, it need to meet the
conditions below.
1) The combination rate for indoor units : Under the 100% of the A2A indoor units + Under the 80% of the DVM Hydro
unit/ Hydro unit HT.
2) A2A indoor units should be operated for cooling mode only, and DVM Hydro unit/ Hydro unit HT should be operated
for heating mode(including floor heating) only.
3) It is not possible to operate A2A indoor units and DVM Hydro unit/ Hydro unit HT at the same time.
4