2.4.4.9. P2 malfunction
P2 display
Low pressure protection
Whether the wiring
between the low pressure
protector and main control
board is connected well or
correctly
Yes
Whether the low
pressure protector
is broken
Method: Disconnect the plug.
Measure the resistance of the
low pressure protector. If the
protector is normal the value is
o
Yes
Check whether the outdoor
ambient temperature is too
low
No
Check whether valve core
of high pressure valve is
opened
Yes
Check if the indoor fan runs
properly in cooling mode
Yes
Replace outdoor main board
No
Refrigerant is not enough add the
refrigerant
No
Check whether the refrigerant
system is ok
Electrical Control System
(For 36k models)
No
Connect it well
Replace low pressure protector
No
Yes
Open fully valve core of
No
high pressure valve
please refer to the solution of fan
speed has been out of control
No
malfunction. Find out the cause and
Stop the unit
have it solved.
Troubleshooting