Leds, Buttons, And Their Meanings - Siemens SIMOCODE pro Manual

Fail-safe digital modules
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

5.2.2

LEDs, buttons, and their meanings

Table 5- 4
LEDs on DM-F PROFIsafe
LED
Status
READY
Off
Green
Flashing green
DEVICE
Off
Green
Red
OUT
Off
Green
Flashing green
SF
Off
Red
1
Yellow
2
Yellow
3
Yellow
4
Yellow
5
Yellow
6
Yellow
7
Yellow
8
Yellow
9
Yellow
10
Yellow
SIMOCODE pro - Fail-Safe Digital Modules
Manual, 11/2017, NEB631679702000/RS-AA/002
Meaning
System interface not connected/supply voltage too low/device defective
Device ON/system interface OK
Device ON/system interface not active or not OK
Supply voltage too low
Device ON
Device defective or faulty
Safety-related output not active
Safety-related output active
Feedback circuit not closed although start condition satisfied
No group fault
Group fault (PROFIsafe not active, incorrect PROFIsafe address, wiring error, device de-
fective)
PROFIsafe address 1
PROFIsafe address 2
PROFIsafe address 4
PROFIsafe address 8
PROFIsafe address 16
PROFIsafe address 32
PROFIsafe address 64
PROFIsafe address 128
PROFIsafe address 256
PROFIsafe address 512