10.5
Monitoring and response times of the DM-F Local fail-safe digital
module
Monitoring and response times of the DM-F LOCAL fail-safe digital module
Table 10- 7
Monitoring and response times of the DM-F LOCAL fail-safe digital module
Monitoring and response times of the DM-F LOCAL fail-safe digital module
Make time (with automatic start)
Make time (with automatic start) after power failure
Make time (monitored start)
Off-delay in case of power failure
Off-delay after opening of the safety circuits
Recovery time after opening of the safety circuits
Recovery time after power failure
Pulse duration
SIMOCODE pro - Fail-Safe Digital Modules
Manual, 11/2017, NEB631679702000/RS-AA/002
10.5 Monitoring and response times of the DM-F Local fail-safe digital module
50 ms (typ.)
•
100 ms (max.)
•
8.0 s (typ.)
•
8.2 s (max.)
•
50 ms (typ.)
•
100 ms (max.)
•
DC: 60 ms (typ.)
•
AC: 200 ms (typ.)
•
50 ms (typ.)
250 ms (typ.)
8.0 s (typ.)
Sensor circuit: 30 ms (min.)
•
Start input 0.2 s (min.)
•
Cascading input: 0.2 s (min.)
•
Technical data
101