Wiring Conditions For Front Connectors - Siemens CPU 313C Hardware And Installation Manual

S7-300 automation system
Hide thumbs Also See for CPU 313C:
Table of Contents

Advertisement

%ULHI RYHUYLHZ RI IURQW FRQQHFWRUV
Table 7-3
&RQQHFWDEOH FDEOHV
solid conductors
flexible conductors
Without wire end
ferrule
With wire end ferrule
Number of conductors per
terminal
Diameter of the conductor
insulation
Stripped length
Wire end ferrules to DIN
46228
Without insulating
collar
With insulating collar
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
A5E00105492-03

Wiring conditions for front connectors

20-pin
No
2
0.25 mm
2
0.25 mm
1 conductor, or 2 conductors
up to 1.5 mm
common wire end ferrule
max. 3.1 mm
6 mm
Version A, 5 mm to 7 mm
length
Version E, up to 6 mm long
)URQW FRQQHFWRU
40-pin
No
2
to 1.5 mm
0.25 mm
2
to 1.5 mm
0.25 mm
1 conductor, or 2 conductors
2
(total) in a
up to 0.75 mm
common wire end ferrule
6 mm
Version A, 5 mm to 7 mm
length
Version E, up to 6 mm long
:LULQJ
2
2
to 0.75 mm
2
2
to 0.75 mm
Potential supply: 1.5 mm
2
(total) in a
max. 2.0 mm for
40 conductors
max. 3.1 mm for 20
conductors
7-3