Creating An Ungrounded Reference Potential On A Cpu - Siemens CPU 313C Hardware And Installation Manual

S7-300 automation system
Hide thumbs Also See for CPU 313C:
Table of Contents

Advertisement


&RQILJXULQJ DQ 6 ZLWK 8QJURXQGHG 5HIHUHQFH 3RWHQWLDO
1RW &38 [&
,QWURGXFWLRQ
If you install an S7-300 with ungrounded reference potential, any interference
currents that occur are dissipated via an RC system to the ground conductor/local
ground integrated into the CPU.
1RWH
An S7-300 with a CPU 31xC cannot be configured ungrounded.
$SSOLFDWLRQ
In extended systems, the S7-300 may require configuration with grounded
reference potential due to ground-fault monitoring. This is the case, for example, in
chemical industry and power stations.
8QJURXQGHG UHIHUHQFH SRWHQWLDO RI &38   DQG  '3
The diagram illustrates an S7-300 configuration with floating reference potential
Figure 5-8 Creating an ungrounded reference potential on a CPU

If you implement an ungrounded reference potential in your CPU: Use a
screwdriver with 3.5 mm blade width and push the grounding slide contact forwards
in the direction of the arrow until it snaps into place.
Ground of internal CPU circuitry


Rail
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
A5E00105492-03
1
7KH GLDJUDP LOOXVWUDWHV XQGHU QXPEHU
10M
<100 nF
L+
M
M
2