shows you the options for addressing specific module channels.
6ORWEDVHG DGGUHVVLQJ
Slot-based addressing is the default setting, that is, 67(3  assigns each slot
number a defined module start address.
8VHUGHILQHG DGGUHVVLQJ
With user-defined addressing, you can assign any module address from the
address area managed by the CPU.

6ORW'HILQHG $GGUHVVLQJ RI 0RGXOHV
,QWURGXFWLRQ
In slot-based addressing (default addressing), a module start address is allocated
to each slot number This is a digital or analog address, depending on the type of
module. This section shows you which module start address is assigned to which
slot number. You need this information to determine the start addresses of the
installed modules.
0D[LPXP DVVHPEO\ DQG WKH FRUUHVSRQGLQJ PRGXOH VWDUW DGGUHVVHV
The figure below shows you an S7-300 assembly on four racks and the optional
slots with their module start addresses.
The input and output addresses for I/O modules start from the same module start
address.
1RWH
With the CPU 31xC, you cannot insert any modules in Slot 11 of Rack 3. The
address area is reserved for the integrated I/O.