Power Supply - Emerson Rosemount 2051 Quick Start Manual

Pressure transmitter / flowmeter transmitter, with foundation protocol
Hide thumbs Also See for Rosemount 2051:
Table of Contents

Advertisement

Quick Start Guide
Note
Do NOT ground the cable shield at the transmitter; if the cable shield touches the
transmitter housing, it can create ground loops and interfere with communications.
b. Continuously connect the cable shields to the power supply ground.
c. Connect the cable shields for the entire segment to a single good earth
ground at the power supply.
Note
Improper grounding is the most frequent cause of poor segment communications.
3. Replace the housing cover. It is recommended that the cover be tightened
until there is no gap between the cover and the housing.
4. Plug and seal unused conduit connections.

Power supply

The transmitter requires between 9 and 32 V dc (9 and 30 V dc for intrinsic safety,
and 9 and 17.5 V dc for FISCO intrinsic safety) to operate and provide complete
functionality.
Power conditioner
A fieldbus segment requires a power conditioner to isolate the power supply,
filter, and decouple the segment from other segments attached to the same
power supply.
Grounding
Signal wiring of the fieldbus segment can not be grounded. Grounding out one of
the signal wires will shut down the entire fieldbus segment.
Shield wire ground
To protect the fieldbus segment from noise, grounding techniques for shield wire
require a single grounding point for shield wire to avoid creating a ground loop.
Connect the cable shields for the entire segment to a single good earth ground at
the power supply.
Signal termination
For every fieldbus segment a terminator should be installed at the beginning and
at the end of each segment.
12
October 2014