Compressor Lock - Daikin FLKS25BAVMB Service Manual

Inverter pair floor / ceiling suspended dual type flk(x)s-ba series
Hide thumbs Also See for FLKS25BAVMB:
Table of Contents

Advertisement

SiBE05-722EE

4.12 Compressor Lock

E6
Error Code
Method of Error
A compressor lock is detected by checking the compressor running condition through the
position detection circuit.
Detection
Error Decision
Conditions
Supposed
Causes
Troubleshooting
Check No.12
Refer to P.104
Check No.15
Refer to P.106
Service Diagnosis
A compressor lock is detected by the current waveform generated when applying high-
frequency voltage to the motor.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Closed stop valve
Compressor locked
Disconnection of compressor harness
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
(Precaution before turning on the power again)
Make sure the power has been off for at least 30 seconds.
Stop valve closed?
NO
Turn off the power. Disconnect the
harnesses U, V, and W.
Check No.15
Check with the inverter analyzer.
Any LED off?
YES
Turn off the power and reconnect
the harnesses. Turn on the power
again and restart the system.
Emergency
stop without compressor
running?
NO
System shut
down after errors repeated
several times?
YES
Refer to P.104
YES
∗ Inverter analyzer:
RSUK0917C
NO
YES
NO
Troubleshooting
Open the stop valve.
Correct the power supply or
replace the outdoor unit
PCB (main PCB).
Replace the compressor.
Check the electronic
expansion valve coil.
Go to Check No. 12.
Replace the compressor.
(R21067)
81

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents