ESIE15-13C
4.34 Transmission Error between Indoor and Outdoor Unit
U4
Remote
Controller
Display
RZQG
Applicable
Models
The error is generated when the micro-processor detects that the transmission between the
Method of Error
indoor and the outdoor unit is not normal over a certain amount of time.
Detection
When the transmission is not carried out normally over a certain amount of time.
Error Decision
Conditions
Wiring indoor-outdoor transmission wire is incorrect
Supposed
Defective indoor unit PCB
Causes
Defective outdoor unit PCB
Burning out fuse
Defective outdoor fan motor
External factor (Noise, etc.)
Defective power supply
Disconnection of optional equipments
Connector is defective (X806A)
Service Diagnosis
Troubleshooting by Remote Controller
173