ESIE15-13C
4.13 Outdoor Unit PCB Abnormality
E1
Remote
Controller
Display
RZQG
Applicable
Models
Micro-computer checks whether E
Method of Error
Detection
When E
Error Decision
Conditions
Defective outdoor unit PCB (A1P)
Supposed
Defective fan motor
Causes
External factor (Noise, etc.)
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Turn OFF the power supply and turn
the power ON.
Is normal
reset possible?
NO
Turn OFF the power supply, remove
the fan motor connector and then turn
the power ON again.
Error is displayed again?
NO
Service Diagnosis
2
PROM error when turning the power supply ON
YES
YES
Troubleshooting by Remote Controller
2
PROM is normal.
External factor (Noise, etc.)
Replace the outdoor unit PCB
(A1P).
Check the fan motor.
139